Diesel generating set GMP110
General specifications
Max power
110 kVA / 88 kW
Cont power
100 kVA / 80 kW
Engine specifications
Type
Perkins
Model
1104C-44TAG2
Cooling
water-cooled
Rate speed
1500 rpm
Engine start
electric starting
Fuel consumption @ 70% (prime)
15.2 l/h
Alternator specifications
Type
Leroy Somer
Model
LSA 44.3 S5
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Type
Mecc Alte
Model
ECP 34-2S/4
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP21
Type
Stamford
Model
UCI274C
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Control panel
Model
GMCA20-04
Dimensions
Open set
Dimensions, LхWхH
2100×1100×1450 mm
Weight
1125 kg
Tank
200 l
Canopy
Dimensions, LхWхH
2550×1100×1700 mm
Weight
1460 kg
Tank
200 l
Noise
68 dB @ 7 m
Note: exterior and technical data are subject to change A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).
To custom-order, please, contact the GMGen Power Systems Commercial Department.
Max power | 110 kVA / 88 kW |
Cont power | 100 kVA / 80 kW |
Type | Perkins |
Model | 1104C-44TAG2 |
Cooling | water-cooled |
Rate speed | 1500 rpm |
Engine start | electric starting |
Fuel consumption @ 70% (prime) | 15.2 l/h |
Type | Leroy Somer |
Model | LSA 44.3 S5 |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Type | Mecc Alte |
Model | ECP 34-2S/4 |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP21 |
Type | Stamford |
Model | UCI274C |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Model | GMCA20-04 |
Dimensions
Open set | |
Dimensions, LхWхH | 2100×1100×1450 mm |
Weight | 1125 kg |
Tank | 200 l |
Canopy | |
Dimensions, LхWхH | 2550×1100×1700 mm |
Weight | 1460 kg |
Tank | 200 l |
Noise | 68 dB @ 7 m |
A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).