Diesel generating set GMP1250
General specifications
Max power
1250 kVA / 1000 kW
Cont power
1125 kVA / 900 kW
Engine specifications
Type
Perkins
Model
4008-30TAG3
Cooling
water-cooled
Rate speed
1500 rpm
Engine start
electric starting
Fuel consumption @ 70% (prime)
159.8 l/h
Alternator specifications
Type
Leroy Somer
Model
LSA 50.2 M6
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Type
Stamford
Model
HCI6K
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Type
Mecc Alte
Model
ECO 43-2M/4
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Control panel
Model
GMCA20-04
Dimensions
Open set
Dimensions, LхWхH
4450×2200×2260 mm
Weight
9250 kg
Note: exterior and technical data are subject to change A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).
To custom-order, please, contact the GMGen Power Systems Commercial Department.
Max power | 1250 kVA / 1000 kW |
Cont power | 1125 kVA / 900 kW |
Type | Perkins |
Model | 4008-30TAG3 |
Cooling | water-cooled |
Rate speed | 1500 rpm |
Engine start | electric starting |
Fuel consumption @ 70% (prime) | 159.8 l/h |
Type | Leroy Somer |
Model | LSA 50.2 M6 |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Type | Stamford |
Model | HCI6K |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Type | Mecc Alte |
Model | ECO 43-2M/4 |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Model | GMCA20-04 |
Dimensions
Open set | |
Dimensions, LхWхH | 4450×2200×2260 mm |
Weight | 9250 kg |
A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).
To custom-order, please, contact the GMGen Power Systems Commercial Department.