Diesel generating set GMP200
General specifications
Max power
200 kVA / 160 kW
Cont power
180 kVA / 144 kW
Engine specifications
Type
Perkins
Model
1106A-70TAG3
Cooling
water-cooled
Rate speed
1500 rpm
Engine start
electric starting
Fuel consumption @ 70% (prime)
27.6 l/h
Alternator specifications
Type
Leroy Somer
Model
LSA 46.3 S2
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Type
Mecc Alte
Model
ECO 38-1S/4
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP21
Type
Stamford
Model
UCI274G
Phase
3
Voltage
230/400 V, 50 Hz
Protection
IP23
Control panel
Model
GMCA20-04
Dimensions
Open set
Dimensions, LхWхH
2400×850×1500 mm
Weight
1770 kg
Tank
220 l
Canopy
Dimensions, LхWхH
3630×1130×2010 mm
Weight
2470 kg
Tank
300 l
Noise
68 dB @ 7 m
Note: exterior and technical data are subject to change A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).
To custom-order, please, contact the GMGen Power Systems Commercial Department.
Max power | 200 kVA / 160 kW |
Cont power | 180 kVA / 144 kW |
Type | Perkins |
Model | 1106A-70TAG3 |
Cooling | water-cooled |
Rate speed | 1500 rpm |
Engine start | electric starting |
Fuel consumption @ 70% (prime) | 27.6 l/h |
Type | Leroy Somer |
Model | LSA 46.3 S2 |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Type | Mecc Alte |
Model | ECO 38-1S/4 |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP21 |
Type | Stamford |
Model | UCI274G |
Phase | 3 |
Voltage | 230/400 V, 50 Hz |
Protection | IP23 |
Model | GMCA20-04 |
Dimensions
Open set | |
Dimensions, LхWхH | 2400×850×1500 mm |
Weight | 1770 kg |
Tank | 220 l |
Canopy | |
Dimensions, LхWхH | 3630×1130×2010 mm |
Weight | 2470 kg |
Tank | 300 l |
Noise | 68 dB @ 7 m |
A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).