Diesel generating set GMP250

Diesel generating set GMP250

  • Photo of diesel genset GMP250.
  • Photo of diesel genset GMP250 in canopy.
  • Photo of diesel genset GMP250.
  • Photo of diesel genset GMP250 in canopy.

General specifications

Max power 250 kVA / 200 kW
Cont power 225 kVA / 180 kW

Engine specifications

Type Perkins
Model 1206A-E70TTAG2
Cooling water-cooled
Rate speed 1500 rpm
Engine start electric starting
Fuel consumption @ 70% (prime) 32.9 l/h

Alternator specifications

Type Leroy Somer
Model LSA 46.3 S4
Phase 3
Voltage 230/400 V, 50 Hz
Protection IP23

Type Mecc Alte
Model ECO 38-3SN/4
Phase 3
Voltage 230/400 V, 50 Hz
Protection IP21
Type Stamford
Model UCDI274K
Phase 3
Voltage 230/400 V, 50 Hz
Protection IP23

Control panel

Model GMCA20-04

Dimensions

Open set
Dimensions, LхWхH 2500×1050×1700 mm
Weight 2100 kg
Tank 265 l
Canopy
Dimensions, LхWхH 3630×1130×2010 mm
Weight 2750 kg
Tank 300 l
Noise 68 dB @ 7 m
Note: exterior and technical data are subject to change

A complete set configuration can be made to custom order with required specifications (a combination of the engine, generator, control panel, power parameters, dimensions, noise muffling level, fuel tank size, etc.).

To custom-order, please, contact the GMGen Power Systems Commercial Department.